{"product_id":"abb-2csr255080r3324-ds201-c32-ac300","title":"ABB 2CSR255080R3324 DS201 C32 AC300 1P+N Residual Current Breaker with Overcurrent (RCBO)","description":"\u003cp\u003eThe 2CSR255080R3324, ABB's DS201 C32 AC300, is a 1P+N RCBO in two DIN-rail modules rated 32 A on a C tripping curve, combining overload and short-circuit protection with 300 mA Type AC residual current sensitivity against sinusoidal earth fault currents. Rated at 240 V AC, it carries a 6 kA breaking capacity and adds direct and indirect contact protection.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCatalog No\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDS201 C32 AC300\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSKU\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2CSR255080R3324\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSeries\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eResidual Current Circuit Breakers with Overcurrent Protection (RCBO)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Current (In)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e32 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Operational Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e240 V AC (acc. to IEC 60898-1)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Frequency\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTripping Characteristic\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eType of Residual Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eType AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Residual Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e300 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Short-Circuit Capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e6 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Ultimate Short-Circuit Breaking Capacity (Icu)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Conditional Short-Circuit Current (Inc)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Service Short-Circuit Breaking Capacity (Ics)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e7.5 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Poles\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1P+N\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Insulation Voltage (Ui)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e500 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Impulse Withstand Voltage (Uimp)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOvervoltage Category\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIII\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower Loss\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e9.9 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDegree of Protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP20 \/ IP40\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Modules\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x H x D)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e35 x 85 x 69 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e200 g\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEAN\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e8012542049616\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eIEC\/EN 61009-1\u003c\/li\u003e\n\u003cli\u003eIEC\/EN 61009-2-1\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe 2CSR255080R3324 covers the 32 A point in the DS201 C-curve range, appropriate where the downstream cable and connected load exceed the 20 A variant but do not need the 40 A version's capacity. Its C tripping characteristic (5-10x In instantaneous) tolerates the inrush of motor or ballast loads. Type AC residual detection is for sinusoidal AC earth faults only - loads producing smoothed DC leakage currents require a Type A device instead.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":50229003387163,"sku":"2CSR255080R3324","price":57.72,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/abb-2csr255080r3324-ds201-c32-ac300-rcbo.jpg?v=1790959413","url":"https:\/\/stoklink.com\/products\/abb-2csr255080r3324-ds201-c32-ac300","provider":"Stoklink","version":"1.0","type":"link"}