{"product_id":"abb-2csa275103r1164-ds-arc1-m-c16-a30","title":"ABB 2CSA275103R1164 DS-ARC1 M C16 A30 1P+N Arc Fault Detection Device (AFDD)","description":"\u003cp\u003eThe 2CSA275103R1164, ABB's DS-ARC1 M C16 A30, is a 1P+N AFDD with built-in RCBO rated 16 A on a C tripping curve, delivering 30 mA Type A residual current protection plus detection of series, parallel and earth arc faults. It occupies 3 DIN-rail modules, operates at 230-240 V AC, and has a 10 kA ultimate short-circuit breaking capacity.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCatalog No\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDS-ARC1 M C16 A30\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSKU\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2CSA275103R1164\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSeries\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAFDD+RCBO (Arc Fault Detection Devices with Integrated Overcurrent and Residual Current Protection)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Current (In)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e16 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Operational Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e230-240 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Frequency\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50-60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTripping Characteristic\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eType of Residual Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eType A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Residual Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e30 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Ultimate Short-Circuit Breaking Capacity (Icu)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Residual Breaking Capacity (IΔm)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e6 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Service Short-Circuit Breaking Capacity (Ics)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e7.5 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Poles\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1P+N\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Insulation Voltage (Ui)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e500 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Impulse Withstand Voltage (Uimp)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOvervoltage Category\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIII\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower Loss\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.1 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDegree of Protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP20 terminals \/ IP40 housing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Modules\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x H x D)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e52.5 x 85 x 69 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e240 g\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEAN\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e8012542611011\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eIEC\/EN 62606\u003c\/li\u003e\n\u003cli\u003eIEC\/EN 61009-1\u003c\/li\u003e\n\u003cli\u003eIEC\/EN 61009-2-1\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003e2CSA275103R1164 covers the 16 A point in the DS-ARC1 M C-curve range, a common rating for lighting and socket circuits where the 10 A or 13 A variants would be undersized. Its C tripping characteristic (5-10x In instantaneous) rides through switching transients from ballasts or small inductive loads that a B curve would trip on. Selecting this 16 A unit over the 20 A sibling keeps the circuit's fault-current let-through lower for a given cable size, since the device's 30 mA Type A RCBO and arc-fault detection stay unchanged across the range.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":50229367865627,"sku":"2CSA275103R1164","price":244.08,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/abb-2csa275103r1164-ds-arc1-m-c16-a30-afdd.png?v=1790958908","url":"https:\/\/stoklink.com\/products\/abb-2csa275103r1164-ds-arc1-m-c16-a30","provider":"Stoklink","version":"1.0","type":"link"}