{"product_id":"abb-1sda100528r1-xt5h-400-ekip-dip-ls-i-in-400-4p-f-f","title":"ABB 1SDA100528R1 XT5H 400 Ekip Dip LS\/I In=400 4p F F 70kA Molded Case Circuit Breaker (MCCB)","description":"\u003cp\u003eThe ABB 1SDA100528R1 is a Tmax XT5H 400 moulded case circuit breaker with an Ekip Dip LS\/I electronic release, rated In 400 A across four poles with front terminals. Short-circuit performance class H gives it a 70 kA breaking capacity at 415 V AC, and the LS\/I release adds overload (L), short-time delay (S) and instantaneous (I) protection functions in one electronic trip unit.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003eSKU\u003c\/td\u003e\n\u003ctd\u003e1SDA100528R1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eTmax XT\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCatalog Designation\u003c\/td\u003e\n\u003ctd\u003eXT5H 400 Ekip Dip LS\/I In=400 4p F F\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEAN\u003c\/td\u003e\n\u003ctd\u003e8056221006040\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSub-type\u003c\/td\u003e\n\u003ctd\u003eXT5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Poles\u003c\/td\u003e\n\u003ctd\u003e4P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Current (In)\u003c\/td\u003e\n\u003ctd\u003e400 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Uninterrupted Current (Iu)\u003c\/td\u003e\n\u003ctd\u003e400 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelease\u003c\/td\u003e\n\u003ctd\u003eEkip Dip LS\/I (electronic, type EL)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShort-Circuit Performance Level\u003c\/td\u003e\n\u003ctd\u003eH\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Type\u003c\/td\u003e\n\u003ctd\u003eAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Operational Voltage (Ue)\u003c\/td\u003e\n\u003ctd\u003e690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Insulation Voltage (Ui)\u003c\/td\u003e\n\u003ctd\u003e1000 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Impulse Withstand Voltage (Uimp)\u003c\/td\u003e\n\u003ctd\u003e8 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Ultimate Breaking Capacity (Icu)\u003c\/td\u003e\n\u003ctd\u003e100 kA at 220-240 V AC, 70 kA at 380-415 V AC, 65 kA at 440 V AC, 50 kA at 500-525 V AC, 40 kA at 690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Service Breaking Capacity (Ics)\u003c\/td\u003e\n\u003ctd\u003eequal to Icu at all listed voltages\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Short-Time Withstand Current (Icw)\u003c\/td\u003e\n\u003ctd\u003e5 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Loss\u003c\/td\u003e\n\u003ctd\u003e19 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Frequency\u003c\/td\u003e\n\u003ctd\u003e50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (W x H x D)\u003c\/td\u003e\n\u003ctd\u003e186 x 205 x 103.5 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet Weight\u003c\/td\u003e\n\u003ctd\u003e6.4 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\u003cli\u003eIEC\/EN 60947-2\u003c\/li\u003e\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe Ekip Dip LS\/I release on the 1SDA100528R1 combines long-time overload (L), short-time delay (S) and instantaneous (I) protection in a single electronic trip unit, giving adjustable time-current curves that a fixed TMA thermomagnetic release cannot match. Short-circuit performance class H lifts both Icu and Ics to 70 kA at 415 V AC with a 5 kA short-time withstand (Icw), so the breaker can hold a fault for a set delay and let a downstream device clear first. Pick this 400 A variant over the 630 A XT5H when the connected load and its upstream protection are sized at or below 400 A; both share the same frame, release family and H performance class.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":50229069971739,"sku":"1SDA100528R1","price":1115.13,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/abb-1sda100528r1-xt5h-400-ekip-dip-ls-i-mccb.png?v=1790958513","url":"https:\/\/stoklink.com\/products\/abb-1sda100528r1-xt5h-400-ekip-dip-ls-i-in-400-4p-f-f","provider":"Stoklink","version":"1.0","type":"link"}