{"product_id":"abb-1sda073031r1-e2-2h-2000-ekip-dip-li-4p-wmp","title":"ABB 1SDA073031R1 E2.2H 2000 Ekip Dip LI 4p WMP 100kA Air Circuit Breaker","description":"\u003cp\u003eThis is the moving part for an ABB SACE Emax 2 E2.2H 2000 air circuit breaker, part number 1SDA073031R1, built as a four-pole unit with the Ekip Dip LI electronic release. Rated current is 2000 A and breaking capacity is 100 kA at 400 V AC; as a WMP it needs a separately ordered fixed part before it can be fitted in a panel.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSKU\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1SDA073031R1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSeries\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSACE Emax 2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCatalog Designation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eE2.2H 2000 Ekip Dip LI 4p WMP\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEAN\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e8015644768812\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFrame \/ Performance Level\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eE2.2H (level H)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePoles\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNeutral Pole Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100% of In\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Current (In \/ Iu)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2000 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Operational Voltage (Ue)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Insulation Voltage (Ui)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1000 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Impulse Withstand Voltage (Uimp)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Ultimate Breaking Capacity (Icu) at 400 V AC\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Service Breaking Capacity (Ics) at 400 V AC\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100 kA (100% of Icu)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Short-Time Withstand Current (Icw)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e85 kA \/ 1 s, 66 kA \/ 3 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRelease \/ Trip Unit\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEkip Dip LI\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eConnecting Capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1800 mm²\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower Loss (per pole)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e450 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x H x D)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e407 x 425 x 383 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e55 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSuitable for IT Networks\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eYes, up to 690 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eWithout the S function, this Ekip Dip LI release clears a short-circuit immediately rather than waiting for a downstream breaker, so it suits a feeder or main where this is the only protective device in the fault path. At 100 kA Icu \/ 85 kA Icw for 1 second it is built on the H performance level, above the N-level frame that is sized for lower fault currents. Ordering a WMP means budgeting for the matching fixed part separately — the pair is what gives the installed breaker its withdrawable, cradle-mounted form for maintenance without disturbing wiring. The neutral pole switches along with the three phases, unlike the 3-pole WMP in the same frame and current.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":50228982677787,"sku":"1SDA073031R1","price":5585.71,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/abb-1sda073031r1-e2-2h-2000-ekip-dip-li-4p-wmp-air-circuit-breaker.jpg?v=1790954495","url":"https:\/\/stoklink.com\/products\/abb-1sda073031r1-e2-2h-2000-ekip-dip-li-4p-wmp","provider":"Stoklink","version":"1.0","type":"link"}