ABB 1SDA072052R1 - SACE Emax 2 E1.2B air circuit breaker moving part, 630 A, 3-pole, Ekip Dip LSI, 42 kA Icu at 400 V AC.
The ABB 1SDA072052R1 is the E1.2B performance level B withdrawable moving part of the SACE Emax 2 air circuit breaker, rated 630 A across 3 poles with an Ekip Dip LSI electronic release. It delivers 42 kA ultimate breaking capacity (Icu) at 400 V AC and 42 kA short-time withstand (Icw) for 1 s, for use up to 690 V AC in drawout switchboard applications.
This 630 A, 3-pole moving part's Ekip Dip LSI release adds the short-time delay stage missing from the LI variant, so its 42 kA/1 s Icw can be used to hold a fault open long enough for a downstream breaker to clear first. Choose it over the LI version wherever the installation needs that coordination step at 630 A; where it does not, the LI variant is the simpler release. It is a drawout moving part and needs the matching withdrawable fixing part to complete the installation.
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|
| Product Net Width | 278 mm |
|---|---|
| Product Net Height | 363.5 mm |
| Product Net Depth / Length | 271 mm |
| Product Net Weight | 18 kg |
| Product Main Type | SACE Emax 2 |
|---|---|
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| Part number | 1SDA072052R1 |
|---|---|
| Type designation | E1.2B |
| Brand | ABB |
| Condition | New, factory sealed |
| Source | ABB and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 8015644759025 |
| ETIM class | EC000228 |
| eCl@ss | 27370409 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Connecting Capacity | 400 mm² |
|---|---|
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle, Ue = 500 ... 690 V 8000 cycle, 30 cycles per hour |
| Mechanical Durability | 20000 cycle, 60 cycles per hour |
| Number of Poles | 3P |
| Power Loss | 62 W |
| Rated Current (In) | 630 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 42 kA, (230 V AC) 42 kA, (380 V AC) 42 kA, (400 V AC) 42 kA, (415 V AC) 42 kA, (440 V AC) 42 kA, (500 V AC) 42 kA, (660 V AC) 42 kA, (690 V AC) 42 kA |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA, for 3 s 24 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 42 kA, (415 V AC) 42 kA, (440 V AC) 42 kA, (500 V AC) 42 kA, (525 V AC) 42 kA, (690 V AC) 42 kA |
| Rated Uninterrupted Current (Iu) | 630 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | B |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
|---|---|
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Package Level 1 Units | box 1 piece |
|---|---|
| Package Level 1 Width | 270 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 20 kg |
| Package Level 1 EAN | 8015644759025 |
| Shipping weight | 18.0 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 02 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of E1.2B is 630 A.
The rated operational voltage of E1.2B is 690 V AC.
The tariff (HS) code on file for E1.2B is 853620.
The EAN (GTIN) of E1.2B is 8015644759025.
E1.2B ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.