{"product_id":"abb-1sda071672r1-e2-2s-2000-ekip-dip-lsi-4p-f-hr","title":"ABB 1SDA071672R1 E2.2S 2000 Ekip Dip LSI 4p F HR 85kA Air Circuit Breaker","description":"\u003cp\u003eABB 1SDA071672R1 is a fixed-mount, rear-horizontal-terminal four-pole SACE Emax 2 E2.2S 2000 Ekip Dip LSI air circuit breaker, rated 2000 A with 85 kA ultimate breaking capacity at 400 V AC. The LSI release adds a settable short-time delay to the overload and instantaneous protection for coordinated, selective tripping.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSKU\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1SDA071672R1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSeries\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSACE Emax 2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCatalog Designation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eE2.2S 2000 Ekip Dip LSI 4p F HR\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEAN\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e8015644755225\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFrame\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eE2.2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBreaking Capacity Performance Level\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Current (In)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2000 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Poles\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNeutral Pole Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100% of Iu\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Operational Voltage (Ue)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Insulation Voltage (Ui)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1000 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Impulse Withstand Voltage (Uimp)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12 kV (IEC 60947-2)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eUltimate Breaking Capacity (Icu, 400 V AC)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e85 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eService Breaking Capacity (Ics, 400 V AC)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e85 kA (100% of Icu)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eShort-Time Withstand Current (Icw)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e66 kA for 1 s \/ 50 kA for 3 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRelease \/ Trip Unit\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEkip Dip LSI\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eVersion\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFixed, rear horizontal terminals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTerminal Connection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eRear flat horizontal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTerminal Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eBolted\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eConnecting Capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1800 mm²\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSuitable for IT Networks\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eYes, up to 690 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower Loss\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e212 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e53 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x H x D)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e366 x 371 x 270 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe fixed body with rear horizontal terminals suits a board wired for direct busbar entry from behind, and its 212 W power loss runs well below the equivalent WMP unit since there is no plug-in contact stack. With the LSI release's short-time delay, this breaker can stay closed through a downstream fault long enough for a smaller breaker to clear it, making it a reasonable main-incomer choice at 2000 A - the LI-only sibling 1SDA071671R1 in the same body style trips instantaneously instead. Icu is 85 kA at 400 V AC, matching the S-level WMP units in this frame.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":50228969701659,"sku":"1SDA071672R1","price":4644.09,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/abb-1sda071672r1-e2-2s-2000-ekip-dip-lsi-4p-f-hr-air-circuit-breaker.jpg?v=1790954030","url":"https:\/\/stoklink.com\/products\/abb-1sda071672r1-e2-2s-2000-ekip-dip-lsi-4p-f-hr","provider":"Stoklink","version":"1.0","type":"link"}