Monitoring Relays for Generators and ATS Systems
How phase-sequence, voltage/frequency and temperature monitoring relays let an ATS safely transfer a load onto a standby generator and back.
The ABB 1SCA153523R1001 (OXB400E3X4QB) is a three-pole TruONE open-style automatic transfer switch rated 400 A, built to switch between two AC sources from 200 to 480 V. A Level 4 touchscreen controller runs the delayed I-O-II transition, and the bottom-supply / top-load terminal layout suits switchboards fed from below.
This 3-pole, 400 A unit leaves the neutral common between sources instead of switching it, the same arrangement as the DIP and LCD controller versions on this frame. Icw of 25 kA for 0.3 s and Uimp of 12 kV exceed the 250 A chassis figures, margin worth checking against the upstream protection before downsizing. Stepping up to the Level 4 touch controller adds a graphical HMI with event history and parameter access, where the Level 2 and Level 3 units on the same chassis rely on DIP switches or a basic text display. QB terminals bring supply in from the bottom and send load out the top; the QT version reverses this for top-fed switchboards.
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|
| Degree of Protection | Front IP20 |
|---|---|
| Pollution Degree | 3 |
| Product Net Width | 390 mm, 15.35 in |
|---|---|
| Product Net Height | 305 mm, 12.01 in |
| Product Net Depth / Length | 183 mm, 7.2 in |
| Product Net Weight | 15.6 kg, 34.39 lb |
| Part number | 1SCA153523R1001 |
|---|---|
| Type designation | OXB400E3X4QB |
| Brand | ABB |
| Condition | New, factory sealed |
| Source | ABB and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 6417019845494 |
| ETIM class | EC000216 |
| eCl@ss | 27371403 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Controller Type | Level 4 (Touch) |
|---|---|
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 400 A |
| Handle Type | Direct Mount |
| Number of Poles | 3P |
| Position of Line Terminals | Supplies on Bottom - Load on Top |
| Power Loss | at Rated Operating Conditions per Pole 20.3 W, Total 60.9 W |
| Rated Frequency (f) | Main Circuit 50-60 Hz |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Current AC-31B (Ie) | (200 … 415 V AC) 400 A |
| Rated Operational Current AC-32B (Ie) | (200 … 415 V AC) 400 A |
| Rated Operational Current AC-33B (Ie) | (200 … 415 V AC) 400 A |
| Rated Operational Voltage | Main Circuit 200...480 V AC |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.3 s 25 kiloampere rms |
| Special Functions | Open style |
| Standards | IEC60947-6-1 |
| Terminal Type | Bolt |
| Transition Type | Delayed |
| ETIM 10 | EC000216 - Switch disconnector (AC) |
|---|---|
| eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Package Level 1 Units | box 1 piece |
|---|---|
| Package Level 1 Width | 345 mm, 13.58 in |
| Package Level 1 Depth / Length | 445 mm, 17.52 in |
| Package Level 1 Height | 240 mm, 9.45 in |
| Package Level 1 Gross Weight | 16.3 kg, 35.94 lb |
| Package Level 1 EAN | 6417019845494 |
| Shipping weight | 15.6 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 02 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of OXB400E3X4QB is 400 A.
The rated operational voltage of OXB400E3X4QB is 200–480 V AC.
The tariff (HS) code on file for OXB400E3X4QB is 853650.
The EAN (GTIN) of OXB400E3X4QB is 6417019845494.
OXB400E3X4QB ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
How phase-sequence, voltage/frequency and temperature monitoring relays let an ATS safely transfer a load onto a standby generator and back.