Monitoring Relays for Generators and ATS Systems
How phase-sequence, voltage/frequency and temperature monitoring relays let an ATS safely transfer a load onto a standby generator and back.
ABB's 1SCA153464R1001 (OXB250E3X4QT) is a three-pole, 250 A TruONE automatic transfer switch for two independent AC sources rated 200 to 480 V. The Level 4 touchscreen controller runs the delayed I-O-II transfer sequence, and the top-supply / bottom-load terminal arrangement fits switchboards fed from an overhead riser.
Keeping the neutral common between sources, this 3-pole 250 A unit skips the switched-neutral function of the 4P S-series frame, the same logic as the other X-series controllers on this chassis. The Level 4 touch controller is the top end of the three options here, trading the DIP switches of the Level 2 unit and the text display of the Level 3 unit for a full graphical HMI with parameter and event access. Icw of 18 kA for 0.3 s and Uimp of 8 kV match the rest of the 250 A frame regardless of controller. QT terminals feed supply from the top and load from the bottom, the mirror of the QB unit, for installations with overhead cable entry.
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|
| Degree of Protection | Front IP20 |
|---|---|
| Pollution Degree | 3 |
| Product Net Width | 330 mm, 12.99 in |
|---|---|
| Product Net Height | 305 mm, 12.01 in |
| Product Net Depth / Length | 183 mm, 7.2 in |
| Product Net Weight | 14.15 kg, 31.2 lb |
| Part number | 1SCA153464R1001 |
|---|---|
| Type designation | OXB250E3X4QT |
| Brand | ABB |
| Condition | New, factory sealed |
| Source | ABB and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 6417019844909 |
| ETIM class | EC000216 |
| eCl@ss | 27371403 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Controller Type | Level 4 (Touch) |
|---|---|
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 250 A |
| Handle Type | Direct Mount |
| Number of Poles | 3P |
| Position of Line Terminals | Supplies on Top - Load on Bottom |
| Power Loss | at Rated Operating Conditions per Pole 9.7 W, Total 29.1 W |
| Rated Frequency (f) | Main Circuit 50-60 Hz |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Current AC-31B (Ie) | (200 … 415 V AC) 250 A |
| Rated Operational Current AC-32B (Ie) | (200 … 415 V AC) 250 A |
| Rated Operational Current AC-33B (Ie) | (200 … 415 V AC) 250 A |
| Rated Operational Voltage | Main Circuit 200...480 V AC |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.3 s 18 kiloampere rms |
| Special Functions | Open style |
| Standards | IEC60947-6-1 |
| Terminal Type | Bolt |
| Transition Type | Delayed |
| ETIM 10 | EC000216 - Switch disconnector (AC) |
|---|---|
| eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Package Level 1 Units | box 1 piece |
|---|---|
| Package Level 1 Width | 345 mm, 13.58 in |
| Package Level 1 Depth / Length | 445 mm, 17.52 in |
| Package Level 1 Height | 240 mm, 9.45 in |
| Package Level 1 Gross Weight | 14.85 kg, 32.74 lb |
| Package Level 1 EAN | 6417019844909 |
| Shipping weight | 14.15 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 02 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of OXB250E3X4QT is 250 A.
The rated operational voltage of OXB250E3X4QT is 200–480 V AC.
The tariff (HS) code on file for OXB250E3X4QT is 853650.
The EAN (GTIN) of OXB250E3X4QT is 6417019844909.
OXB250E3X4QT ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
How phase-sequence, voltage/frequency and temperature monitoring relays let an ATS safely transfer a load onto a standby generator and back.